Architectural Specification for Conceal Ceiling
Suspension System
A) Suspension System
- The Suspension system for gypsum board shall be
Conceal Ceiling Suspension System, Ceiling
Pattern A
and complying with JIS A6517 standard
- The ceiling furrings shall be made of hot-dip
galvanized steel. The cross sectional dimension of CC-25 Carrying Channel and CW-25 Double
Furring shall be 38 x 12 x 1.6mm and 50 x 25 x 0.5mm respectively.
- As an alternative proposal, the supporting
calculation shall be submitted and approved by the Architect to ensure that the
structural is adequate to sustain the ceiling load.
B) Suspension System
- Gypsum board shall be Gypsum Board of size 4' x 8' x
5/8" thick with tapered edges and complying with ASTM C36 and BS 1230 Standard.
C) Installation
- Installation of the 9mm dia. threaded suspension both shall
be fixed by suitable insert to the underneath of slab soffit. Spacing of suspension both
must be at 1200m Max. in either direction and at perimeter of ceiling as required.
- The carrying channel must be placed at 1200mm Max. shall be
hung to the lower part of the suspension bolts by means of galvanized steel hangers and
nuts.
- The double furring at a spacing of 407mm Max. shall be fixed
to the carrying channel with double clips at each intersection. Double clips must as a
rule alternate with the sides of the carrying channel.
- Rigid and aligned system for the fixing of ceiling board
must be provided with separated pieces of carrying channel and double furring to be
jointed by channel joint and double joint respectively.
- Extra hangers to be provided where opening are required for
light fittings and access panels.
- All components must be well fixed and the suspension system
must be correctly aligned and accurately leveled before attaching the ceiling board.
- The gypsum board shall be fixed by S25 screws at 300m Max.
to the double furring with long edges of the gypsum board placed parallel to the double
furring.
- Finish of all joints and screw heads with joint tape and
Goldkote joint tape compound must be in accordance with manufacturer's instruction which
shall be approved by the Architect and sand smooth.
- Plastering and Painting works can be proceeded.
Ceiling
Installation Pattern