Downward loading Test

dwg14.jpg (14871 bytes)

  1. Downward Loading Test for Furring Channels ( Type 25 ). As shown above, the two furring channels at  the center should have deflection values measured after being load continuously for 5 minutes on to a piece of plywood board of 450 x 450 x 15mm placed on them.
  2. The furring channels were tested with the loading of 50 kgf (490.33 N). The deflection values were derived from each channel and the larger value was taken. The residual deflection was measured after unloading.

    dwg16.jpg (22289 bytes)

  3. Downward Loading Test for Furring Channels ( Type CC-25 ). As shown above, the two furring channels at the center point between the suspension bolts should have the maximum deflection values measured after being loaded with 75 kgf ( 735.50 N) continuously for 5 minutes onto a piece of plywood board of 1200 x 400 x 30mm placed on them. The deflection values were derived from each carrying channel, and the larger was taken. The residual deflection value was also measured after unloading.

    dwg15.jpg (23364 bytes)

Upward loading Test

Ceiling materials were duly assembled as shown above, with additional installation of a piece of gypsum
board 9mm thick prescribed as JIS A 6901 ceiling material. In the center of the ceiling, a piece of plywood
of 450 x 450 x 15mm was placed underneath, and the upward successive loading tests with 30 kgf
( 294.2 N ) were applied for 5 minutes. The maximum deflection values were measured in the centered in the
center of each furring channel, and the larger value was taken.

Item / Type

Type 25 Test needed
Zinc volume galvanized ( 1 ) Minimum 120 g/m2 ( both face ) Zinc Volume
Stability of component in shape Lateral bend 2L/1000mm or less Component's lateral bend & Camber
Camber

Load sustainable

Downward load Furring Channel Maximum deflection 10mm or less Maximum residual deflection 2mm or less Downward loading
Carrying Channel Maximum deflection 5mm or less Maximum residual deflection 2mm or less Downward loading
Upward load Maximum deflection 5mm or less Upward loading

Note: (1) Zinc volume galvanized shall be in accordance with JIS G3302.