Downward loading Test
|
|
|
Upward loading Test
Ceiling materials were duly assembled as shown above, with
additional installation of a piece of gypsum
board 9mm thick prescribed as JIS A 6901 ceiling material. In the center of the ceiling, a
piece of plywood
of 450 x 450 x 15mm was placed underneath, and the upward successive loading tests with 30
kgf
( 294.2 N ) were applied for 5 minutes. The maximum deflection values were measured in the
centered in the
center of each furring channel, and the larger value was taken.
Item / Type |
Type 25 | Test needed | |
| Zinc volume galvanized ( 1 ) | Minimum 120 g/m2 ( both face ) | Zinc Volume | |
| Stability of component in shape | Lateral bend | 2L/1000mm or less | Component's lateral bend & Camber |
| Camber | |||
Load sustainable |
|||
| Downward load | Furring Channel | Maximum deflection 10mm or less Maximum residual deflection 2mm or less | Downward loading |
| Carrying Channel | Maximum deflection 5mm or less Maximum residual deflection 2mm or less | Downward loading | |
| Upward load | Maximum deflection 5mm or less | Upward loading | |
Note: (1) Zinc volume galvanized shall be in accordance with JIS G3302.